All citations for Abbington Vlge Nrsg & Rhb Ctr
State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.
Last standard health inspection on record
April 22, 2026
Showing 26 to 50 of 74 citations
No harm, with potential for more than minimal harm
Provide properly protected cooking facilities.
The home gave a date the problem would be corrected (June 19, 2026).
No harm, with potential for more than minimal harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
The home gave a date the problem would be corrected (May 22, 2026).
No harm, with potential for more than minimal harm
Install corridor and hallway doors that block smoke.
The home gave a date the problem would be corrected (May 22, 2026).
No harm, with potential for more than minimal harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
The home gave a date the problem would be corrected (May 22, 2026).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (May 22, 2026).
No harm, with potential for more than minimal harm
Ensure food and drink is palatable, attractive, and at a safe and appetizing temperature.
The home gave a date the problem would be corrected (November 18, 2025).
No harm, with potential for more than minimal harm
Reasonably accommodate the needs and preferences of each resident.
The home gave a date the problem would be corrected (September 19, 2025).
No harm, with potential for more than minimal harm
Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
The home gave a date the problem would be corrected (March 6, 2025).
No harm, with potential for more than minimal harm
Ensure each resident has a room at or above ground level.
The home gave a date the problem would be corrected (March 19, 2025).
No harm, with potential for more than minimal harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Have stairways and smokeproof enclosures used as exits that meet safety requirements.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Have properly located and lighted "Exit" signs.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Have an enclosure around a vertical opening shaft.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Install smoke barrier doors that can resist smoke for at least 20 minutes.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Ensure precautions for handling oxygen cylinders and equipment are correctly followed.
The home gave a date the problem would be corrected (March 12, 2025).
No harm, with potential for more than minimal harm
Provide care and assistance to perform activities of daily living for any resident who is unable.
The home gave a date the problem would be corrected (March 15, 2024).
No harm, with potential for more than minimal harm
Have a policy regarding use and storage of foods brought to residents by family and other visitors.
The home gave a date the problem would be corrected (March 15, 2024).
No harm, with potential for more than minimal harm
Have stairways and smokeproof enclosures used as exits that meet safety requirements.
The home gave a date the problem would be corrected (March 22, 2024).
No harm, with potential for more than minimal harm
Have properly located and lighted "Exit" signs.
The home gave a date the problem would be corrected (March 22, 2024).
No harm, with potential for more than minimal harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
The home gave a date the problem would be corrected (March 21, 2024).
No harm, with potential for more than minimal harm
Install an approved automatic sprinkler system.
The home gave a date the problem would be corrected (March 22, 2024).
No harm, with potential for more than minimal harm
Install corridor and hallway doors that block smoke.
The home gave a date the problem would be corrected (March 22, 2024).
Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.