All citations for Abundant Acres Care and Rehab

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Abundant Acres Care and Rehab

Last standard health inspection on record

August 21, 2025

Showing 1 to 14 of 14 citations

  1. Immediate jeopardy to resident health or safety

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level L.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  2. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  3. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  4. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  6. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  7. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  8. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  10. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  11. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  13. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).

  14. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 4, 2025).