All citations for Arc at Bradley

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Arc at Bradley

Last standard health inspection on record

May 17, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 17 of 17 citations

  1. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2024).

  2. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 5, 2024).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 5, 2024).

  4. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 23, 2024).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  6. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    A waiver was granted (July 2, 2024).

  7. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 30, 2024).

  8. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    A waiver was granted (July 26, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 4, 2024).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 7, 2024).

  11. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 10, 2024).

  12. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 10, 2024).

  13. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 12, 2024).

  14. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 10, 2024).

  15. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 23, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2024).

  17. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 23, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.