All citations for Arlington Residence and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Arlington Residence and Rehabilitation Center

Last standard health inspection on record

April 9, 2026

Showing 1 to 7 of 7 citations

  1. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

  2. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

  3. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

  4. No harm, with potential for more than minimal harm

    Have properly sized and located compartments to protect residents from smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0371, Smoke Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

  5. No harm, with potential for more than minimal harm

    Have an externally vented heating system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0522, Services Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

  7. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of April 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 24, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.