All citations for Atlantic Specialty Care

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Atlantic Specialty Care

Last standard health inspection on record

April 9, 2026

Showing 1 to 8 of 8 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 27, 2025).

  2. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  4. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  5. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  6. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  7. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  8. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.