All citations for Autumn Lake Healthcare at Beloit

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Autumn Lake Healthcare at Beloit

Last standard health inspection on record

February 12, 2026

Showing 1 to 8 of 8 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  2. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  4. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  7. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

  8. No harm, with potential for minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of February 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.