All citations for Azria Health Great Bend

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Azria Health Great Bend

Last standard health inspection on record

July 29, 2025

Showing 1 to 14 of 14 citations

  1. Immediate jeopardy to resident health or safety

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level L.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  2. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  3. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  4. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  5. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  6. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  7. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    A waiver was granted (May 10, 2022).

  8. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  10. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  11. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  12. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  14. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 5, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.