All citations for Bayside of Poquoson Health and Rehab

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Bayside of Poquoson Health and Rehab

Last standard health inspection on record

August 29, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 6 of 6 citations

  1. No harm, with potential for more than minimal harm

    Establish an Emergency Preparedness Program (EP).

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0001, Emergency Preparedness Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 3, 2024).

  2. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 16, 2024).

  3. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 16, 2024).

  4. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 16, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 16, 2024).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 16, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.