All citations for Belknap County Nursing Home

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Belknap County Nursing Home

Last standard health inspection on record

September 4, 2025

Showing 1 to 6 of 6 citations

  1. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2025).

  2. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of September 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2025).

  3. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of September 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2025).

  4. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of September 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2025).

  5. No harm, with potential for minimal harm

    Ensure operating rooms are properly protected and written records are maintained and available for inspection.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0913, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2025).

  6. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 4, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.