All citations for Bentwood Nursing & Rehab

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Bentwood Nursing & Rehab

Last standard health inspection on record

February 24, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  2. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  4. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    A waiver was granted (September 15, 2022).

  6. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    A waiver was granted (September 15, 2022).

  8. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  9. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 29, 2022).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 29, 2022).

  11. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    A waiver was granted (September 15, 2022).

  12. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of May 6, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.