All citations for Bethany Home, Inc

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Bethany Home, Inc

Last standard health inspection on record

June 26, 2025

Showing 1 to 7 of 7 citations

  1. No harm, with potential for more than minimal harm

    Provide family notifications of emergency plan.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0035, Emergency Preparedness Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 8, 2025).

  2. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 22, 2025).

  3. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 22, 2025).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 22, 2025).

  5. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 22, 2025).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 22, 2025).

  7. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 22, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.