All citations for Bettendorf Health Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Bettendorf Health Care Center

Last standard health inspection on record

September 11, 2025

Showing 1 to 6 of 6 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of September 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 17, 2025).

  2. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of September 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2025).

  3. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of September 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2025).

  4. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of September 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 16, 2025).

  5. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 23, 2025).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 15, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.