All citations for Bria of Godfrey

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Bria of Godfrey

Last standard health inspection on record

August 16, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 6 of 6 citations

  1. No harm, with potential for more than minimal harm

    Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0361, Smoke Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2024).

  2. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2024).

  3. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2024).

  4. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2024).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.