All citations for Burgh Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Burgh Care Center

Last standard health inspection on record

April 10, 2026

Showing 1 to 8 of 8 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  2. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  3. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  4. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  5. No harm, with potential for minimal harm

    Address patient/client population and determine types of services needed.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0007, Emergency Preparedness Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  6. No harm, with potential for minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  7. No harm, with potential for minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  8. No harm, with potential for minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of April 5, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).