All citations for Care Pavilion Nursing and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Care Pavilion Nursing and Rehabilitation Center

Last standard health inspection on record

December 22, 2025

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  2. No harm, with potential for more than minimal harm

    Meet requirements for sections of health care facilities separated by fire resistive construction.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0131, Construction Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  3. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  4. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  5. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  6. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    A waiver was granted (April 19, 2025).

  7. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  8. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  9. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  10. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.