All citations for Careone at Middletown

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Careone at Middletown

Last standard health inspection on record

May 26, 2026

Showing 1 to 14 of 14 citations

  1. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

  2. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2025).

  3. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2025).

  4. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2025).

  5. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 2, 2025).

  6. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2025).

  7. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

  8. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2025).

  9. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

  11. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

  12. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0531, Services Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

  13. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2025).

  14. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 2, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.