All citations for Carmel Hills Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Carmel Hills Care Center

Last standard health inspection on record

April 17, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 27, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2026).

  3. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2026).

  4. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 19, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (February 27, 2026).

  5. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  6. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2026).

  7. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  8. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2026).

  10. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  11. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 19, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  12. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 17, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 23, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.