All citations for Cedar Ridge Inn

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Cedar Ridge Inn

Last standard health inspection on record

February 21, 2025

Showing 26 to 36 of 36 citations

  1. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  2. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of September 9, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 21, 2022).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of September 9, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 28, 2022).

  5. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of September 9, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 14, 2022).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  7. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  8. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  9. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  10. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 21, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 18, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.