All citations for Centerville Specialty Care

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Centerville Specialty Care

Last standard health inspection on record

December 4, 2025

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 27, 2023).

  2. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 26, 2023).

  3. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 28, 2023).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 27, 2023).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 28, 2023).

  6. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2023).

  7. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2023).

  8. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2023).

  9. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2023).

  10. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 18, 2023).

  11. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2023).

  12. No harm, with potential for more than minimal harm

    Meet requirements for the use and maintenance of medical gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0922, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 26, 2023).

  13. No harm, with potential for more than minimal harm

    Ensure precautions for handling oxygen cylinders and equipment are correctly followed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0929, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 18, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 26, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.