All citations for City Creek Post Acute

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to City Creek Post Acute

Last standard health inspection on record

July 24, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 27, 2026).

  2. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 21, 2026).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2026).

  4. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 23, 2026).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 29, 2026).

  6. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 24, 2026).

  7. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 14, 2026).

  8. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2026).

  10. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2026).

  11. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of July 24, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.