All citations for Complete Care at Holiday City

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Complete Care at Holiday City

Last standard health inspection on record

April 25, 2025

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  2. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 28, 2023).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  6. No harm, with potential for more than minimal harm

    Have an externally vented heating system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0522, Services Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  7. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  9. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2023).

  10. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 28, 2023).

  11. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.