All citations for Courtyard Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Courtyard Care Center

Last standard health inspection on record

January 31, 2025

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  2. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  4. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  5. No harm, with potential for more than minimal harm

    Establish roles under a Waiver declared by secretary.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0026, Emergency Preparedness Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  6. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  7. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  8. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  9. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  10. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  11. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  12. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.