All citations for Cranberry Place

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Cranberry Place

Last standard health inspection on record

January 31, 2026

Showing 1 to 9 of 9 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0908, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  3. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  4. No harm, with potential for minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  5. No harm, with potential for minimal harm

    Meet other general requirements.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  6. No harm, with potential for minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  7. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  8. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

  9. No harm, with potential for minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of January 31, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 25, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.