All citations for Daughters of Israel Pleasant Valley Home

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Daughters of Israel Pleasant Valley Home

Last standard health inspection on record

March 12, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  2. No harm, with potential for more than minimal harm

    Construct fire resistant interior walls.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0331, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 24, 2026).

  4. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  6. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0531, Services Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 1, 2026).

  8. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  10. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  11. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2026).

  12. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 24, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.