All citations for Divine Rehabilitation and Nursing at Shane Hill

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Divine Rehabilitation and Nursing at Shane Hill

Last standard health inspection on record

June 11, 2026

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2026).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 10, 2026).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 12, 2026).

  4. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 25, 2026).

  5. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 11, 2026).

  6. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 11, 2026).

  7. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 10, 2026).

  8. No harm, with potential for more than minimal harm

    Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0361, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2026).

  10. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.