All citations for East Park Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to East Park Care Center

Last standard health inspection on record

October 28, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 26 to 43 of 43 citations

  1. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  2. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  3. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  5. No harm, with potential for more than minimal harm

    Have an alternate power supply for its alarm system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0344, Smoke Deficiencies. Inspection of October 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 21, 2024).

  6. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of October 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 21, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 21, 2024).

  8. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  9. No harm, with potential for more than minimal harm

    Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0227, Egress Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  10. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  11. No harm, with potential for minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  12. No harm, with potential for minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  13. No harm, with potential for minimal harm

    Develop Emergency Preparedness policies and procedures.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0013, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  14. No harm, with potential for minimal harm

    Establish policies and procedures for volunteers.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0024, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  15. No harm, with potential for minimal harm

    Develop a communication plan.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0029, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  16. No harm, with potential for minimal harm

    Provide a means of sharing information on occupancy/needs.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0034, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  17. No harm, with potential for minimal harm

    Establish emergency prep training and testing.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

  18. No harm, with potential for minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of May 30, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2019).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.