All citations for Fair Acres Geriatric Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Fair Acres Geriatric Center

Last standard health inspection on record

February 13, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  3. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  4. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  5. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  6. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  7. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  8. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  10. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

  11. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 13, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.