All citations for Focused Care at Humble

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Focused Care at Humble

Last standard health inspection on record

July 15, 2026

Showing 1 to 8 of 8 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  3. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  4. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  5. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  6. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  7. No harm, with potential for more than minimal harm

    Ensure precautions for handling oxygen cylinders and equipment are correctly followed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0929, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

  8. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of July 15, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 28, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.