All citations for Froh Community Home

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Froh Community Home

Last standard health inspection on record

June 11, 2026

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2024).

  3. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

  5. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of January 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  6. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of January 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  7. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of January 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

  9. No harm, with potential for more than minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of January 30, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  10. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of May 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.