All citations for Golden Acres Living and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Golden Acres Living and Rehabilitation Center

Last standard health inspection on record

January 22, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 13, 2026).

  3. No harm, with potential for more than minimal harm

    Have an alternate power supply for its alarm system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0344, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  4. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2026).

  6. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 30, 2026).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 13, 2026).

  9. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  10. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  11. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

  12. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 22, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.