All citations for Groton Community Health Care Ctr Res Care Fac
State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.
Last standard health inspection on record
February 6, 2026
Showing 1 to 23 of 23 citations
No harm, with potential for more than minimal harm
Have approved installation, maintenance and testing program for fire alarm systems.
The home gave a date the problem would be corrected (February 14, 2025).
No harm, with potential for more than minimal harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for more than minimal harm
Ensure that testing and maintenance of electrical equipment is performed.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for more than minimal harm
Address subsistence needs for staff and patients.
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for more than minimal harm
Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
The home gave a date the problem would be corrected (February 28, 2025).
No harm, with potential for more than minimal harm
Provide properly protected cooking facilities.
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for more than minimal harm
Inspect, test, and maintain automatic sprinkler systems.
The home gave a date the problem would be corrected (March 3, 2025).
No harm, with potential for more than minimal harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for more than minimal harm
Have simulated fire drills held at unexpected times.
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for more than minimal harm
Have restrictions on the use of portable space heaters.
The home gave a date the problem would be corrected (January 25, 2025).
No harm, with potential for more than minimal harm
Install a two-hour-resistant firewall separation.
The home gave a date the problem would be corrected (February 6, 2025).
No harm, with potential for more than minimal harm
Keep aisles, corridors, and exits free of obstruction in case of emergency.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for more than minimal harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for more than minimal harm
Have stairways and smokeproof enclosures used as exits that meet safety requirements.
The home gave a date the problem would be corrected (January 25, 2025).
No harm, with potential for more than minimal harm
Install emergency lighting that can last at least 1 1/2 hours.
The home gave a date the problem would be corrected (February 14, 2025).
No harm, with potential for more than minimal harm
Have properly located and lighted "Exit" signs.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for more than minimal harm
Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.
The home gave a date the problem would be corrected (February 14, 2025).
No harm, with potential for more than minimal harm
Install corridor and hallway doors that block smoke.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (January 27, 2025).
No harm, with potential for minimal harm
Develop and maintain an Emergency Preparedness Program (EP).
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for minimal harm
Establish policies and procedures for volunteers.
The home gave a date the problem would be corrected (January 24, 2025).
No harm, with potential for minimal harm
Establish staff and initial training requirements.
The home gave a date the problem would be corrected (January 24, 2025).
Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.