All citations for Helen Newberry Joy HLTCU Golden Leaves Living Cent

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Helen Newberry Joy HLTCU Golden Leaves Living Cent

Last standard health inspection on record

August 28, 2025

Showing 26 to 29 of 29 citations

  1. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 28, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2025).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 28, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 27, 2025).

  3. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of August 28, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 26, 2025).

  4. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of August 28, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 15, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.