All citations for Heritage Manor

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Heritage Manor

Last standard health inspection on record

July 31, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  3. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  5. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  6. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  7. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  8. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  9. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0541, Services Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  10. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 16, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 1, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.