All citations for Indianspring of Oakley

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Indianspring of Oakley

Last standard health inspection on record

July 1, 2025

Showing 1 to 7 of 7 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

  4. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

  6. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

  7. No harm, with potential for minimal harm

    Meet the requirements of an integrated health system.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0042, Emergency Preparedness Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.