All citations for La Mesa Healthcare Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to La Mesa Healthcare Center

Last standard health inspection on record

July 15, 2026

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2025).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 29, 2025).

  3. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  4. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  6. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  7. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 9, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 1, 2025).

  9. No harm, with potential for minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2025).

  10. No harm, with potential for minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of March 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2025).