All citations for Linden Grove Health Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Linden Grove Health Care Center

Last standard health inspection on record

January 14, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 29, 2024).

  2. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  4. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  6. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0926, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2024).

  8. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2024).

  9. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 27, 2024).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.