All citations for Little Brook Nursing and Convalescent Home

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Little Brook Nursing and Convalescent Home

Last standard health inspection on record

March 4, 2026

Showing 1 to 14 of 14 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  2. No harm, with potential for more than minimal harm

    Include a process for Emergency Preparedness collaboration.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0009, Emergency Preparedness Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  3. No harm, with potential for more than minimal harm

    Create arrangements with other facilities to receive patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0025, Emergency Preparedness Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  4. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  5. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2023).

  6. No harm, with potential for more than minimal harm

    Provide at least two remote exits on each floor or fire section of the building.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0252, Egress Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    A waiver was granted (August 21, 2023).

  7. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 25, 2023).

  8. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 21, 2023).

  9. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 17, 2023).

  10. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 25, 2023).

  11. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 16, 2023).

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 27, 2023).

  13. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 25, 2023).

  14. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 15, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 25, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.