All citations for Mado Healthcare - Uptown

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Mado Healthcare - Uptown

Last standard health inspection on record

December 12, 2025

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 17, 2023).

  2. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  3. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    Fire Safety Evaluation Survey.

  4. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  6. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  7. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  8. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  9. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  10. No harm, with potential for more than minimal harm

    Have corridors or aisles that are unobstructed and are at least 8 feet in width.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0232, Egress Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    Fire Safety Evaluation Survey.

  11. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  12. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  13. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  14. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  15. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).

  16. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 10, 2023).