All citations for Majestic Care of Jefferson Pointe

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Majestic Care of Jefferson Pointe

Last standard health inspection on record

March 23, 2026

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Meet other general requirements that are deficient.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0300, Egress Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  4. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  5. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  7. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 1, 2025).

  9. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  10. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 1, 2025).

  12. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  13. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  14. No harm, with potential for more than minimal harm

    Have proper fire barriers, ventilation and signs for the transfilling of oxygen.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0927, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  15. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).

  16. No harm, with potential for minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 10, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 18, 2025).