All citations for Majestic Center for Rehab & Sub-Acute Care

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Majestic Center for Rehab & Sub-Acute Care

Last standard health inspection on record

December 19, 2025

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  2. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  3. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  6. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0531, Services Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  7. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0541, Services Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  8. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  9. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

  12. No harm, with potential for more than minimal harm

    Ensure that anesthesia apparatus are tested after any adjustment, modification or repair.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0924, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 3, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 20, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.