All citations for Niagara Rehabilitation and Nursing Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Niagara Rehabilitation and Nursing Center

Last standard health inspection on record

July 15, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    Fire Safety Evaluation Survey (August 27, 2024).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  3. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  5. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  6. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0901, Electrical Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  9. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  10. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  11. No harm, with potential for minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  12. No harm, with potential for minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

  13. No harm, with potential for minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of July 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 28, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.