All citations for Northvine Postacute Care

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Northvine Postacute Care

Last standard health inspection on record

October 25, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 26, 2024).

  3. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 27, 2024).

  4. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  5. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  6. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 7, 2024).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 27, 2024).

  8. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 7, 2024).

  9. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).