All citations for Oakwood Gardens Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Oakwood Gardens Care Center

Last standard health inspection on record

July 2, 2026

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  2. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  3. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  4. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  5. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  6. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  8. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  10. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  11. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  13. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.