All citations for Ozark Care & Rehab Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Ozark Care & Rehab Center

Last standard health inspection on record

December 12, 2024

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  4. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  5. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  7. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  8. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  9. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  10. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

  11. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 12, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.