All citations for Radford Green

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Radford Green

Last standard health inspection on record

April 15, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  2. No harm, with potential for more than minimal harm

    Establish policies and procedures for sheltering.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0022, Emergency Preparedness Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  3. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  4. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  6. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0926, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  8. No harm, with potential for more than minimal harm

    Meet requirements for sections of health care facilities separated by fire resistive construction.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0131, Construction Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0361, Smoke Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  10. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 13, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.