All citations for Rialto Post Acute Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Rialto Post Acute Center

Last standard health inspection on record

January 8, 2026

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  2. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  4. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  6. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  7. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  8. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

  10. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 7, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 20, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.