All citations for Richardson Nursing and Rehabilitation

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Richardson Nursing and Rehabilitation

Last standard health inspection on record

March 12, 2026

Showing 1 to 7 of 7 citations

  1. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  4. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  5. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  6. No harm, with potential for more than minimal harm

    Install properly constructed windows in hallway walls or doors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0364, Smoke Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  7. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 12, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.