All citations for Richmond Healthcare & Rehab Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Richmond Healthcare & Rehab Center

Last standard health inspection on record

February 26, 2025

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  4. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  6. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  7. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  10. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

  11. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of February 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.