All citations for River Ridge Living Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to River Ridge Living Center

Last standard health inspection on record

March 18, 2025

Showing 1 to 17 of 17 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  2. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  3. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 26, 2025).

  4. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  5. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home has a plan to correct it (May 16, 2025).

  6. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home has a plan to correct it (May 16, 2025).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  8. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home has a plan to correct it (May 16, 2025).

  9. No harm, with potential for more than minimal harm

    Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0901, Electrical Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 11, 2025).

  11. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2025).

  12. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  13. No harm, with potential for more than minimal harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0926, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  14. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 12, 2025).

  15. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  16. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

  17. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 16, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.