All citations for Salina Presbyterian Manor

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Salina Presbyterian Manor

Last standard health inspection on record

June 26, 2025

Showing 1 to 12 of 12 citations

  1. Immediate jeopardy to resident health or safety

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level J.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 16, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (March 17, 2026).

  2. Immediate jeopardy to resident health or safety

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Isolated (one or a few residents). CMS level J.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of March 16, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (March 17, 2026).

  3. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  4. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  6. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  7. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  9. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2025).

  11. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 2, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure precautions for handling oxygen cylinders and equipment are correctly followed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0929, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 2, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.